Formula & Engineering Reference
Liquid (turbulent, non-choked):
Gas / vapour (ISA/IEC 60534 universal, N7 = 1360):
with x = ΔP/P1, Y = 1 − x / (3 Fk xT), Fk = k/1.4, choked when x ≥ Fk·xT.
| Symbol | Variable | Unit |
|---|---|---|
| Cv | Flow coefficient (Kv = 0.865·Cv) | US |
| Q | Flow — liquid (gpm) / gas (scfh) | US |
| SG | Liquid specific gravity (water = 1) | — |
| Gg | Gas specific gravity (air = 1) | — |
| ΔP | P1 − P2 across the valve | psi |
| P1 | Inlet absolute pressure | psia |
| T | Inlet absolute temperature | °R |
| xT | Pressure-drop ratio factor | — |
| Y | Gas expansion factor (0.667 ≤ Y ≤ 1) | — |
SI inputs are converted internally to the US units the coefficient is defined in, then Cv and Kv are reported together.
Water, 40 m³/h, P1 = 6 bar a, P2 = 4 bar a, SG = 1.0.
Convert: Q = 40 × 4.403 = 176.1 gpm; ΔP = (6 − 4) × 14.504 = 29.0 psi.
Cv = 176.1 × √(1.0 / 29.0) = 176.1 × 0.1857 = 32.7. Kv = 0.865 × 32.7 = 28.3.
Against typical globe-valve capacities, the smallest valve with rated Cv ≥ 32.7/0.8 = 41 is a 2″ body (rated ≈ 48). At design flow the valve sits near 32.7/48 ≈ 68% open — comfortably in the controllable band.
Preliminary sizing, not a vendor calculation. The recommended size and opening use representative globe-valve Cv values. Final selection must come from the manufacturer's rated Cv and characteristic curve for the specific trim.
Liquid equation is the simplified form. It omits the piping geometry factor FP and the liquid pressure-recovery factor FL. For cavitating or flashing service, the full IEC 60534-2-1 liquid equation with FL and vapour pressure is required — this tool flags a high ΔP/P1 ratio as a prompt to check it.
Gas uses the universal equation. Compressibility Z is taken as 1 (ideal). For high-pressure gas, supply the real Z. The expansion factor Y is clamped at its choked value 0.667, so the Cv at and beyond choke is computed on the choked pressure drop, as the standard requires.
xT and k matter for gas. The pressure-drop ratio factor xT is a valve property (≈0.72 globe, ≈0.30 ball, ≈0.38 butterfly). The specific-heat ratio k sets Fk. Both shift the choke point and the Cv — use values for your actual valve and gas.
Size for the operating window. Aim for the design flow at roughly 60–80% travel. Check the minimum-flow case too: a valve that is 70% open at maximum flow but 5% open at minimum will control poorly at turndown.
Cv is the flow coefficient — the US gpm of 60 °F water that passes through the fully open valve at 1 psi drop. Bigger Cv means more capacity. The metric form is Kv (m³/h at 1 bar), with Kv ≈ 0.865·Cv.
Use Cv = Q√(SG/ΔP) with Q in gpm and ΔP in psi. The tool converts metric inputs for you and reports both Cv and Kv. It assumes turbulent, non-flashing flow; very viscous or cavitating service needs the full IEC corrections.
Gas expands and accelerates through the valve, so density drops across it. The expansion factor Y captures that, and the pressure-drop ratio x is capped at the choked value Fk·xT, beyond which more ΔP yields no more flow. The universal equation with N7 = 1360 (scfh) handles both.
It means the pressure-drop ratio has reached the choke point, so the flow is sonic in the vena contracta. The Cv is then computed on the choked ΔP, not the full ΔP. Adding more pressure drop will not push more gas through — you need a larger valve or a different trim.
An oversized valve controls in the first few percent of travel, where resolution and characteristic are worst. It hunts, gives poor turndown, and wears the seat. Size so design flow lands around 60–80% open. The tool flags an estimated opening below about 20%.
Both describe the same capacity in different units. Cv is US (gpm, psi); Kv is metric (m³/h, bar). Convert with Kv = 0.865·Cv. Match whichever coefficient the valve datasheet quotes when you compare options.
Control Valve Sizing Guide
3 topics • Cv / Kv & ISA/IEC 60534 referenceSizing a control valve is a balancing act. Too small and it cannot pass the maximum flow even wide open; too large and it does all its work in a sliver of travel where control is hopeless. The flow coefficient Cv — and its metric twin Kv — is the language the whole exercise is conducted in. It is simply the capacity of the valve: how much flow it passes per unit of pressure drop. Once you can compute the required Cv at the design conditions, you can compare it against published valve capacities and pick a body and trim that lands in the controllable sweet spot.
The liquid equation is almost trivial; the interesting part is everything around it. Gas brings compressibility and the choked-flow ceiling. Real service brings cavitation, flashing, noise, and the piping geometry factor. This guide separates the clean core equations from the corrections, and explains how the required Cv turns into a valve size and an expected opening.